Go Back To:
TESTERS & MONITORS

CONTROLSTIK II™ SYSTEM

CONTROLSTIK II™ SYSTEM

Engineering Specifications:

Rinse water usage shall be minimized by means of automatic conductivity control systems. They shall consist of a temperature compensated conductivity sensor, corrosion resistant one-inch solenoid valve, and transformer box which safely reduces line power to the sensor. Enclosure shall be fiberglass with heavy rubber gasket and 316 stainless steel. Circuitry shall be solid-state, and unaffected by changes in voltage. Setpoint adjustment shall be on sensor to minimize tampering. Rinse tank controls shall be Myron L Model 597 or approved equal.

 

Transformer Box Specifications:

Input Power Choice of 110 or 220 VAC, 50/60 Hz;
  Automatic voltage regulation insures operation of the systems from 105-125V or 210-250V respectively.
Output 24 volts @ 600 mA AC
Maximum Power Consumption @ 117V: 12 watts (103 milliamps)
Enclosure IP65/NEMA 4X fiberglass case with heavy gasket and 316 stainless steel hardware.
Lights LEDs indicate POWER (red) and VALVE (yellow)
Electrical Installation Either HARDWIRE with 5/8 in. conduit; or PLUG-IN with 8 ft./2,4 meter, 18 ga. 3-conductor plug.
  (supplied with 110V systems only)
Mounting Flange on enclosure for easy wall mounting
Dimensions 184 H x 197 W x 127 D mm/ 7.25 H x 7.75 W x 5 D in.

 

Sensor Specifications:

Ranges 5-500 micromhos (for high quality water)
  500-5000 micromhos (for normal tap water)
Power 1 volt AC (from transformer box)
On-Off Span Approximately 5% of setpoint
Temperature Compensation Automatic to 25°C/77°F up to 82°C/180°F
Materials Epoxy and 316 stainless steel
Cable 10 ft./3 meter 22 ga., 4-conductor, vinyl jacketed
Installation Corrosion-proof ABS bracket supplied
Dimensions 304 L x 25 Dia. mm/12 L x 1 Dia. in.

 

Solenoid Valve Specifications:

Size 1 in. NPT normally closed; compatible with plastic or metal piping
Power 24 volts @ 200 mA AC
  (from transformer box)
Materials Body: glass reinforced nylon
  Diaphragm: nylon reinforced BUNA N synthetic rubber
  All exposed metal: stainless steel
Operating Pressure 10-100 psi / 0,69-6,90 bar
Miscellaneous adjustable flow control
  manual override
  anti-hammer closing
  conduit connector

Data Sheet

Request More Information Now!